Boyard Inverter Condensing Unit BYGF-120-SJL-SZDP – 12 HP
BYGF-120-SJL-SZDP is an inverter condensing unit with a power of 12 HP, designed for installations requiring high cooling capacity and flexible adaptation of the device's operation to the current load. The use of inverter control allows for frequency regulation of the system operation depending on the cooling demand.
The device uses refrigerant R410A and is adapted for three-phase 380 V power supply. With a wide evaporating temperature range from -40°C to -5°C, it can be used in installations requiring both low and higher evaporating temperatures, according to the refrigeration system design.
Main Advantages
- 12 HP Power – for installations with high cooling power demand.
- Inverter Technology – frequency regulation in response to changing load.
- Wide Evaporating Temperature Range – from -40°C to -5°C.
- Refrigerant R410A – designed for systems intended to work with this refrigerant.
- Three-Phase 380 V Power Supply – for appropriately prepared electrical installation.
- Pressure Control – high and low pressure protections, depending on the applied configuration.
- Equipment Customisation – depending on the version, additional elements such as oil separator, accumulator, solenoid valve, or compressor crankcase heater can be applied.
Technical Specifications
Parameter | Value |
|---|
Model | BYGF-120-SJL-SZDP |
Device Type | Inverter Condensing Unit |
Nominal Power | 12 HP |
Power Supply | 3 PH, 380 V, 50/60 Hz |
Refrigerant | R410A |
Evaporating Temperature Range | from -40°C to -5°C |
Control | Inverter, frequency regulation |
Pressure Control | High pressure switch and low pressure switch or sensor, depending on configuration |
Gas Connection Diameter | 1-1/8 inch (28.58 mm) |
Liquid Connection Diameter | 5/8 inch (15.88 mm) |
Product Dimensions | 1200 × 490 × 1570 mm |
Installation Dimensions | 640 × 440 mm |
Cooling Capacity
The cooling capacity of the BYGF-120-SJL-SZDP model depends on the evaporating temperature. According to the manufacturer's table, it is as follows:
Evaporating Temperature | Cooling Capacity |
|---|
-40°C | 6800 W |
-35°C | 8280 W |
-30°C | 10 000 W |
-25°C | 12 200 W |
-20°C | 14 800 W |
-15°C | 18 000 W |
-10°C | 21 800 W |
-5°C | 26 500 W |
The given values refer to the manufacturer's test conditions: ambient temperature 32°C, subcooling 0°C, and suction gas temperature 18°C. Actual performance may vary depending on installation parameters and operating conditions.
Application
The BYGF-120-SJL-SZDP unit can be used in professional refrigeration installations where high performance and the ability to regulate system operation are required. When selecting the device, consider the cooling power demand, evaporating temperature, ambient conditions, and parameters of other installation components.
Why Choose BYGF-120-SJL-SZDP?
The BYGF-120-SJL-SZDP model combines 12 HP power, inverter control, and the ability to operate over a wide range of evaporating temperatures. A maximum cooling capacity of 26.5 kW under specified test conditions makes this unit worth considering for installations with high cooling demand.